480-Watt Intelligent DIN Rail Power Supply with Battery Back Up (UPS Function)

DRS-480

Description

The MEAN WELL DRS-480 series DIN rail UPS power supplies have a full range universal AC input, making them ideal for OEMs producing equipment for global markets. 

In addition to the primary output, there is an additional charging output that will automatically adjust the current depending on the primary output current. Should the AC mains fail, the DRS-240 will switch to powering the load from the back-up battery.  When the AC mains is restored, the power supply will revert to powering the load from the mains supply and will recharge the battery. 

The power supplies are suitable for charging lead-acid and lithium-ion batteries.  To allow for remote monitoring, alarm signals are provided for AC Fail, Battery Low, Charger Fail, and DC OK. You can also opt for either a built-in MODBus or CANBus interface for remote status monitoring and control. With the CANBus version you can also set the output charging curve, charging voltage, and charging current via the MEAN WELL SBP-001 battery charger programmer (ordered separately).  

The DRS-240 series power supplies have a wide operating temperature range (refer to derating curve in data sheet), making these power supplies suitable for a wide range of applications. 

Refer to table below for models in the range:

Image
Certification CB
Image
Certification CE
Image
IC RCM
Image
3 Year Warranty
MEAN WELL DRS-480-24

Images are for reference only, refer to product data sheet

Models in this series

Output

Input

DC Voltage Power Rated Current Input Efficiency Input Voltage
DRS-480-24 (MODBus) 24V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 20A 92.50% 90 ~ 305VAC
DRS-480-24CAN (CANBus) 24V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 20A 92.50% 90 ~ 305VAC
DRS-480-36 (MODBus) 36V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 13.3A 93.50% 90 ~ 305VAC
DRS-480-36CAN (CANBus) 36V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 13.3A 93.50% 90 ~ 305VAC
DRS-480-48 (MODBus) 48V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 10A 93.50% 90 ~ 305VAC
DRS-480-48CAN (CANBus) 48V Combined power on all Channels must not exceed 480W, load has priority. 550W peak capability within 5s. 10A 93.50% 90 ~ 305VAC